SIPLUS HMI OP 73

Overview

  • Operator panel for operation and monitoring of machines and systems
  • Graphics in a new dimension: small and smart
  • Pixel-graphics 3″ LCD, monochrome
  • 8 system keys, 4 freely configurable function keys
  • All interfaces (e.g. MPI, PROFIBUS DP) are on-board
  • SIPLUS OP 73 is the successor of the Operator Panel OP3
Note:

SIPLUS extreme products are based on Siemens Industry standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.

SIPLUS HMI OP 73

Order number

6AG1 641-0AA11-4AX0

Order number based on

6AV6 641-0AA11-0AX0

Ambient temperature range

0 … +50 °C

Conformal coating

Coating of the printed circuit boards and the electronic components

Technical data

The technical data of the standard product applies except for the ambient conditions.

Ambient conditions

Relative humidity

100%, condensation/frost permissible. No commissioning if condensation present.

Biologically active substances, compliance with EN 60721-3-3

Class 3B2 mold spores, fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation!

Chemically active substances, compliance with EN 60721-3-3

Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation!

Mechanically active substances, compliance with EN 60721-3-3

Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation!

Air pressure (depending on the highest positive temperature range specified)

1080 … 795 hPa (-1000 … +2000 m)
see ambient temperature range

795 … 658 hPa (+2000 … +3500 m)
derating 10 K

658 … 540 hPa (+3500 … +5000 m)
derating 20 K

 

Benefits

  • High-contrast display for good readability
  • Large keys for high operational safety
  • Simple handling and configuring
  • Integral component of Totally Integrated Automation (TIA):
    Increases productivity, minimizes the engineering outlay, reduces the lifecycle costs
  • Service-friendly through maintenance-free design (no battery) and high service life of the backlighting
  • Graphics library is available complete with ready-to-use display objects
  • Can be used worldwide:
    • 32 languages can be configured (incl. Asian and Cyrillic character sets)
    • Up to 5 languages are selectable online
    • Language-dependent texts and graphics

Application

The OP 73 Operator Panels can be used wherever direct operator control and monitoring of machines and installations is required locally – whether in production automation, process automation or building automation. They are in use in an extensive range of sectors and applications.

Compatibility with OP3
  • Same installation cutout as OP3
  • The OP3 configurations can be loaded from ProTool/Lite, ProTool and ProTool/Pro

Migration manual with description of the important differences over OP3 or ProTool

Design

  • 3? LCD, 160 x 48 pixels, monochrome
  • 8 system keys, 4 user-configurable function keys
  • Numerical and alphanumeric input option via cursor keys
  • Compact design with low mounting depth
  • Rugged plastic housing
  • The front is resistant to various oils, greases and standard detergents
  • Plug-type terminals for a 24 V DC power supply
  • RS 485 interface for process connections (MPI, PROFIBUS DP up to 1.5 Mbit/s) and for configuration download

Function

  • Input/output fields
    for displaying and changing process parameters
  • Function keys
    are used for directly triggering functions and actions. Up to 16 functions can be configured simultaneously on function keys.
  • Graphics
    can be used as icons instead of text to “label” function keys or buttons. They can also be used as simple on-screen graphics.
    In the configuration tool, a library is available containing an extensive range of graphics and a wide variety of objects. All editors with an OLE interface can be used as graphics editors (such as PaintShop, Designer or CorelDraw).
  • Predefined
    for labeling function keys, process pictures and process values in different font sizes
  • Bars are used for the graphical display of dynamic values
  • Language selection during runtime
    • 5 online languages, 32 configuration languages incl. Asian and Cyrillic character sets
    • Language-dependent texts and graphics
  • User administration (security)
    • Authentication with user ID and password
    • User-group-specific rights
  • Signaling systemHelp texts
    • Discrete alarms
    • Analog alarms
    • Freely definable message classes (e.g., status/fault messages) for definition of acknowledgment response and display of message events
    • Message history
  • for process images, messages and variables
  • Arithmetic functions
  • Limit value monitoring
    for reliable process control of inputs and outputs
  • Indicator light
    for machine and plant status indication
  • Scheduler for global function execution
  • Template concept;
    Creation of screen templates (picture elements configured in the template appear in every screen)
  • Simple maintenance and configuration thanks to:
    • Backup and restoration of configuration, operating system and firmware on a PC using ProSave
    • Configuration download via MPI/PROFIBUS DP or serially via RS485
    • Individual contrast settings
    • No batteries are necessary
Configuration

Configuration is performed using the SIMATIC WinCC flexible Compact, Standard or Advanced engineering software, Version 2004 SP1 plus HSP or higher, or with the SIMATIC WinCC Comfort engineering software (TIA Portal), V11 or higher.

For more information about engineering software, see HMI software/engineering software SIMATIC WinCC flexible/WinCC (TIA Portal).

Integration

The OP 73 can be connected to:

  • SIMATIC S7-200/-300/-400
  • SIMATIC WinAC Software/Slot PLC

Note:

For further information, see “System interfaces”.

Technical specifications

6AG1 641-0AA11-4AX0

OP 73

Display

Screen diagonal

3 in

Size

3″

Display type

STN, black/white

Resolution (pixels)

  • Resolution (WxH in pixel)

160 x 48

Backlighting

  • MTBF backlighting (at 25 °C)

100 000 h

Control elements

Control elements

Membrane keyboard

Function keys, programmable

4 function keys

Connection for mouse/keyboard/barcode reader

- / - / -

Keyboard

    • Number of system keys

8

Touch operation

  • Design as touch screen

No

Supply voltage

Type of supply voltage

DC

Input current

Rated current

0.1 A

Processor

Processor type

ARM

Memory

Usable memory for user data

256 kbyte

Time of day

Clock

  • Type

Software clock, no battery backup

  • Hardware clock (real-time clock)

No

  • Software clock

Yes

  • Battery-backed

No

  • Synchronizable

No

Interfaces

Interfaces

1 x RS485 (max. 1.5 Mbit/s)

Degree and class of protection

Front

IP65

IP (rear)

IP20

Standards, approvals, certificates

CE mark

Yes

KC approval

Yes

EAC (formerly Gost-R)

Yes

Suitable for safety functions

No

Use in hazardous areas

  • EX zone 2

No

  • EX zone 22

No

Ambient conditions

Mounting position

vertical

maximum permissible angle of inclination without external ventilation

+/- 80 °

Operating temperature

  • Operation

0 °C to +50 °C

Storage/transport temperature

  • Transport, storage

-20 °C to +60 °C

Relative humidity

  • Operation, max.

100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)

Extended ambient conditions

  • Relative to ambient temperature-atmospheric pressure-installation altitude

Tmin  … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin …  (Tmax - 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin …  (Tmax - 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m)

  • Relative humidity

    • with condensation, maximum

100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)

  • Resistance

    • against biologically active substances

Yes;  Class 3B2 mold, fungus and dry rot spores (with the exception of  fauna). The supplied connector covers must remain on the unused  interfaces during operation!

    • against chemically active substances

Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!

    • against mechanically active substances

Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!

Operating systems

Operating system

LINUX

Configuration

Configuration software

  • Configuration tool

WinCC flexible Compact Version 2004 SP 1 or higher; HSP OP 73 (to be ordered separately)

Languages

Online languages

  • Number of online/runtime languages

5

Functionality under WinCC (TIA Portal)

Libraries

Yes

Task planner

Yes

Message system

  • Number of messages

500

  • Bit messages

Yes

  • Analog messages

Yes

Variables

  • Number of variables per device

1 000

  • Limit values

Yes

  • Multiplexing

Yes

Images

  • Number of configurable images

500

Image objects

  • Text objects

1,000 text elements

  • Graphics object

Bit maps, icons, icon (full-screen)

Complex image objects

  • Status/control

Not possible

  • dynamic objects

Bar graphs

Lists

  • Number of text lists per project

150

  • Number of graphics lists per project

0

Security

  • Number of user groups

50

  • Number of user rights

32

  • Password export/import

Yes

Transfer (upload/download)

  • Transfer of configuration

MPI/PROFIBUS DP, serial, automatic transfer recognition

Process coupling

  • Connection to controller

S7-200, S7- 300/400, Win AC see section on ”System interfaces”

Expandability/openness

  • Open Platform Program

No

Dimensions

Width of the housing front

154 mm

Height of housing front

84 mm

Weights

Weight (without packaging)

0.25 kg

Dimensional drawings