SIPLUS HMI OP 73 |
|
---|---|
Order number |
6AG1 641-0AA11-4AX0 |
Order number based on |
6AV6 641-0AA11-0AX0 |
Ambient temperature range |
0 … +50 °C |
Conformal coating |
Coating of the printed circuit boards and the electronic components |
Technical data |
The technical data of the standard product applies except for the ambient conditions. |
Ambient conditions |
|
Relative humidity |
100%, condensation/frost permissible. No commissioning if condensation present. |
Biologically active substances, compliance with EN 60721-3-3 |
Class 3B2 mold spores, fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation! |
Chemically active substances, compliance with EN 60721-3-3 |
Class 3C4 incl. salt spray in accordance with EN60068-2-52 (degree of severity 3). The supplied plug covers must remain in place over the unused interfaces during operation! |
Mechanically active substances, compliance with EN 60721-3-3 |
Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Air pressure (depending on the highest positive temperature range specified) |
1080 … 795 hPa (-1000 … +2000 m) 795 … 658 hPa (+2000 … +3500 m) 658 … 540 hPa (+3500 … +5000 m) |
Benefits
- High-contrast display for good readability
- Large keys for high operational safety
- Simple handling and configuring
- Integral component of Totally Integrated Automation (TIA):
Increases productivity, minimizes the engineering outlay, reduces the lifecycle costs - Service-friendly through maintenance-free design (no battery) and high service life of the backlighting
- Graphics library is available complete with ready-to-use display objects
- Can be used worldwide:
- 32 languages can be configured (incl. Asian and Cyrillic character sets)
- Up to 5 languages are selectable online
- Language-dependent texts and graphics
Application
The OP 73 Operator Panels can be used wherever direct operator control and monitoring of machines and installations is required locally – whether in production automation, process automation or building automation. They are in use in an extensive range of sectors and applications.
Compatibility with OP3
- Same installation cutout as OP3
- The OP3 configurations can be loaded from ProTool/Lite, ProTool and ProTool/Pro
Migration manual with description of the important differences over OP3 or ProTool
Design
- 3? LCD, 160 x 48 pixels, monochrome
- 8 system keys, 4 user-configurable function keys
- Numerical and alphanumeric input option via cursor keys
- Compact design with low mounting depth
- Rugged plastic housing
- The front is resistant to various oils, greases and standard detergents
- Plug-type terminals for a 24 V DC power supply
- RS 485 interface for process connections (MPI, PROFIBUS DP up to 1.5 Mbit/s) and for configuration download
Function
- Input/output fields
for displaying and changing process parameters - Function keys
are used for directly triggering functions and actions. Up to 16 functions can be configured simultaneously on function keys. - Graphics
can be used as icons instead of text to “label” function keys or buttons. They can also be used as simple on-screen graphics.
In the configuration tool, a library is available containing an extensive range of graphics and a wide variety of objects. All editors with an OLE interface can be used as graphics editors (such as PaintShop, Designer or CorelDraw). - Predefined
for labeling function keys, process pictures and process values in different font sizes - Bars are used for the graphical display of dynamic values
- Language selection during runtime
- 5 online languages, 32 configuration languages incl. Asian and Cyrillic character sets
- Language-dependent texts and graphics
- User administration (security)
- Authentication with user ID and password
- User-group-specific rights
- Signaling systemHelp texts
- Discrete alarms
- Analog alarms
- Freely definable message classes (e.g., status/fault messages) for definition of acknowledgment response and display of message events
- Message history
- for process images, messages and variables
- Arithmetic functions
- Limit value monitoring
for reliable process control of inputs and outputs - Indicator light
for machine and plant status indication - Scheduler for global function execution
- Template concept;
Creation of screen templates (picture elements configured in the template appear in every screen) - Simple maintenance and configuration thanks to:
- Backup and restoration of configuration, operating system and firmware on a PC using ProSave
- Configuration download via MPI/PROFIBUS DP or serially via RS485
- Individual contrast settings
- No batteries are necessary
Configuration
Configuration is performed using the SIMATIC WinCC flexible Compact, Standard or Advanced engineering software, Version 2004 SP1 plus HSP or higher, or with the SIMATIC WinCC Comfort engineering software (TIA Portal), V11 or higher.
For more information about engineering software, see HMI software/engineering software SIMATIC WinCC flexible/WinCC (TIA Portal).
Integration
The OP 73 can be connected to:
- SIMATIC S7-200/-300/-400
- SIMATIC WinAC Software/Slot PLC
Note:
For further information, see “System interfaces”.
Technical specifications
|
6AG1 641-0AA11-4AX0 |
|
OP 73 |
Display |
|
Screen diagonal |
3 in |
Size |
3″ |
Display type |
STN, black/white |
Resolution (pixels) |
|
|
160 x 48 |
Backlighting |
|
|
100 000 h |
Control elements |
|
Control elements |
Membrane keyboard |
Function keys, programmable |
4 function keys |
Connection for mouse/keyboard/barcode reader |
- / - / - |
Keyboard |
|
|
8 |
Touch operation |
|
|
No |
Supply voltage |
|
Type of supply voltage |
DC |
Input current |
|
Rated current |
0.1 A |
Processor |
|
Processor type |
ARM |
Memory |
|
Usable memory for user data |
256 kbyte |
Time of day |
|
Clock |
|
|
Software clock, no battery backup |
|
No |
|
Yes |
|
No |
|
No |
Interfaces |
|
Interfaces |
1 x RS485 (max. 1.5 Mbit/s) |
Degree and class of protection |
|
Front |
IP65 |
IP (rear) |
IP20 |
Standards, approvals, certificates |
|
CE mark |
Yes |
KC approval |
Yes |
EAC (formerly Gost-R) |
Yes |
Suitable for safety functions |
No |
Use in hazardous areas |
|
|
No |
|
No |
Ambient conditions |
|
Mounting position |
vertical |
maximum permissible angle of inclination without external ventilation |
+/- 80 ° |
Operating temperature |
|
|
0 °C to +50 °C |
Storage/transport temperature |
|
|
-20 °C to +60 °C |
Relative humidity |
|
|
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
Extended ambient conditions |
|
|
Tmin … Tmax at 1080 hPa … 795 hPa (-1000 m … +2000 m) // Tmin … (Tmax - 10K) at 795 hPa … 658 hPa (+2000 m … +3500 m) // Tmin … (Tmax - 20K) at 658 hPa … 540 hPa (+3500 m … +5000 m) |
|
|
|
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
|
|
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
|
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation! |
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Operating systems |
|
Operating system |
LINUX |
Configuration |
|
Configuration software |
|
|
WinCC flexible Compact Version 2004 SP 1 or higher; HSP OP 73 (to be ordered separately) |
Languages |
|
Online languages |
|
|
5 |
Functionality under WinCC (TIA Portal) |
|
Libraries |
Yes |
Task planner |
Yes |
Message system |
|
|
500 |
|
Yes |
|
Yes |
Variables |
|
|
1 000 |
|
Yes |
|
Yes |
Images |
|
|
500 |
Image objects |
|
|
1,000 text elements |
|
Bit maps, icons, icon (full-screen) |
Complex image objects |
|
|
Not possible |
|
Bar graphs |
Lists |
|
|
150 |
|
0 |
Security |
|
|
50 |
|
32 |
|
Yes |
Transfer (upload/download) |
|
|
MPI/PROFIBUS DP, serial, automatic transfer recognition |
Process coupling |
|
|
S7-200, S7- 300/400, Win AC see section on ”System interfaces” |
Expandability/openness |
|
|
No |
Dimensions |
|
Width of the housing front |
154 mm |
Height of housing front |
84 mm |
Weights |
|
Weight (without packaging) |
0.25 kg |
Dimensional drawings